SIL PFDavg calculator (1oo1, 1oo2, 2oo3)

Estimate the average probability of failure on demand (PFDavg) of a safety function and the SIL band it falls in.

Inputs

Results

Use a decimal point or decimal comma, with no thousands separators. Scientific notation (for example 1.5e-3) is accepted. Change any unit with the selector next to the value.

How it works

Choose the voting architecture, enter the dangerous undetected failure rate λDU (in FIT, failures per 10⁹ hours), the proof-test interval and the common-cause factor β. The tool calculates PFDavg with the simplified equations and the corresponding SIL band for low-demand mode.

Low-demand SIL bands (IEC 61508-1 Table 2, IEC 61511-1 Table 4)

Safety integrity levelPFDavg (low demand)Risk reduction factor (RRF)
SIL 110⁻² ≤ PFDavg < 10⁻¹10 – 100
SIL 210⁻³ ≤ PFDavg < 10⁻²100 – 1 000
SIL 310⁻⁴ ≤ PFDavg < 10⁻³1 000 – 10 000
SIL 410⁻⁵ ≤ PFDavg < 10⁻⁴10 000 – 100 000

Formulas

PFDavg (1oo1) = λDU · T / 2
1oo2: ((1 − β) · λDU · T)² / 3 + β · λDU · T / 2
2oo2: λDU · T
2oo3: ((1 − β) · λDU · T)² + β · λDU · T / 2

Worked example

A shutdown valve has λDU = 100 FIT (1 × 10⁻⁷ /h) and is proof tested once a year (8 760 h). Compare 1oo1 with 1oo2 at β = 10 %.

  1. 1oo1: PFDavg = 1 × 10⁻⁷ × 8 760 / 2 = 4.38 × 10⁻⁴ (RRF 2 283) - SIL 3 band.
  2. 1oo2: ((0.9 × 10⁻⁷)² × 8 760²)/3 + 0.1 × 10⁻⁷ × 8 760 / 2 = 2.07 × 10⁻⁷ + 4.38 × 10⁻⁵ = 4.40 × 10⁻⁵ (RRF 22 700).
  3. The common-cause term is 99.5 % of the 1oo2 result.

Result: 1oo1 4.38 × 10⁻⁴; 1oo2 4.40 × 10⁻⁵ - common cause dominates redundant systems.

Assumptions and limits

  • A teaching estimate, not a SIL verification. It uses the simplified equations for one component group and ignores diagnostics, repair time, partial-stroke tests, imperfect proof tests and the final element's own data. A real SIL claim also needs architectural constraints, systematic capability and a lifecycle assessment under IEC 61508 and IEC 61511.
  • λDU is per identical channel, not for the whole safety function. Channels have synchronized, complete proof tests; one year is 8,760 hours. β must be the effective common-cause fraction for the selected architecture. This tool limits λDU × T to 0.1 and assesses only the selected component group, not the complete safety loop.

Frequently asked questions

What PFDavg does each SIL need?

In low-demand mode: SIL 1 from 10⁻² to 10⁻¹, SIL 2 from 10⁻³ to 10⁻², SIL 3 from 10⁻⁴ to 10⁻³ and SIL 4 from 10⁻⁵ to 10⁻⁴.

Why does a redundant system not improve by a factor of 10?

Common-cause failures (β) defeat both channels at once; with β = 10 % the common-cause term usually dominates.

Is this a SIL verification?

No. A SIL claim also needs hardware fault tolerance, systematic capability and the safety lifecycle of IEC 61511. Use the SIL Verification Worksheet for a full low-demand calculation.

What is a FIT?

One failure in 10⁹ device-hours. 100 FIT = 1 × 10⁻⁷ per hour.

How does the proof-test interval affect PFDavg?

For 1oo1, PFDavg grows linearly with the interval: doubling the interval doubles the PFDavg.

References

  • IEC 61508-6:2010, Annex B (simplified equations).
  • IEC 61511-1:2016+AMD1:2017, Functional safety - Safety instrumented systems for the process industry sector.
  • ISA-TR84.00.02-2015, Safety Integrity Level (SIL) Verification of Safety Instrumented Functions.

For education and quick estimates. Shared by the Oil-Gas.net Engineering Working Group as general practitioner guidance; not a standard and provided without warranty. Check every result against the governing standards, vendor data and your project or site requirements before design, operation or safety decisions.