4-20 mA scaling calculator (linear and square root)

Scale a 4-20 mA transmitter signal to its process value and percent of range, or work out the current you should see for a given value. Choose linear scaling or square-root scaling for differential-pressure flow loops. The tool also flags signals outside the NAMUR NE 43 measuring range.

Inputs

Results

Use a decimal point or decimal comma, with no thousands separators. Scientific notation (for example 1.5e-3) is accepted. Change any unit with the selector next to the value.

How it works

Enter the lower and upper range values (LRV and URV) configured in the transmitter or the control system, in any engineering unit. Then choose what you know: the current in mA, the process value or the percent of signal.

With linear scaling, the signal is proportional to the process value: 4 mA is the LRV and 20 mA is the URV. With square-root scaling, the signal is proportional to differential pressure, and flow is proportional to the square root of differential pressure, so 25 % of signal is 50 % of flow.

The LRV may be larger than the URV (a reverse range). The result uses the same unit you used for the range.

Formulas

Signal fraction from current:

s = (I − 4) / 16

Linear scaling:

PV = LRV + s · (URV − LRV)

Square-root scaling (DP flow):

PV = LRV + √s · (URV − LRV)      and back:  s = ((PV − LRV) / (URV − LRV))²

Current from signal fraction:

I = 4 + 16 · s

Symbols: I = loop current (mA); s = signal fraction (0 at 4 mA, 1 at 20 mA); PV = process value; LRV, URV = lower and upper range values.

Worked example

A 0-10 bar(g) pressure transmitter reads 13.6 mA. What is the pressure? And what if the same current came from a 0-500 m³/h DP flow loop with square-root scaling?

Inputs: LRV = 0; URV = 10 bar(g); I = 13.6 mA.

  1. Signal fraction s = (13.6 − 4) / 16 = 0.6, i.e. 60 % of signal.
  2. Linear: PV = 0 + 0.6 × (10 − 0) = 6 bar(g).
  3. Square root (flow loop 0-500 m³/h): √0.6 = 0.7746, so flow = 0.7746 × 500 = 387.3 m³/h.

Result: 6 bar(g) for the linear pressure loop; 387.3 m³/h (77.46 % of flow) for the square-root flow loop.

Assumptions and limits

  • Applies to the analogue 4-20 mA signal of a two-wire or four-wire transmitter. HART digital values are not included.
  • Square-root scaling assumes flow is proportional to √ΔP, as for orifice plates, venturis and nozzles at constant density. Pitot-type and averaging tubes follow the same law; check vendor data for other elements.
  • Square-root extraction magnifies noise near zero flow. Most systems apply a low-flow cut-off (often 1 % to 6 % of flow); this tool does not.
  • NAMUR NE 43 limits used: measuring range 3.8 to 20.5 mA; failure signal at or below 3.6 mA or at or above 21.0 mA. Your system may use other alarm thresholds.

Frequently asked questions

What is 12 mA in a 4-20 mA loop?

12 mA is the midpoint of the signal: 50 % of range with linear scaling. With square-root scaling for DP flow, 12 mA is 50 % of differential pressure, which is about 70.7 % of flow.

Why does a 4-20 mA signal start at 4 mA and not 0 mA?

The live zero lets the receiver tell a real zero reading from a broken wire or a dead transmitter (0 mA), and it leaves enough current to power a two-wire transmitter.

What do 3.6 mA and 21 mA mean?

Under NAMUR NE 43 a transmitter drives its output to 3.6 mA or below, or 21 mA or above, to report a failure. Values between 3.8 and 20.5 mA are treated as valid measurements, including slight under- and over-range.

Should I do the square root in the transmitter or in the DCS?

Do it in one place only. If the transmitter outputs a flow-linear signal, set the DCS input to linear; extracting the root twice is a common commissioning error.

How do I convert mA to percent?

Percent of signal = (mA − 4) / 16 × 100. For example, 8 mA is 25 % and 16 mA is 75 %.

References

  • IEC 60381-1:1982, Analogue signals for process control systems - Part 1: Direct current signals.
  • NAMUR NE 43 (2003 edition), Standardization of the signal level for the failure information of digital transmitters.
  • ISO 5167-1:2022, Measurement of fluid flow by means of pressure differential devices - Part 1: General principles (flow proportional to the square root of differential pressure).

For education and quick estimates. Shared by the Oil-Gas.net Engineering Working Group as general practitioner guidance; not a standard and provided without warranty. Check every result against the governing standards, vendor data and your project or site requirements before design, operation or safety decisions.